The new DURAG D-LX 100 Compact Flame Monitor is the first system of its kind to
meet current American and European flame monitoring standards. The
D-LX 100 was
designed for continuous, intermittent and 72-hour operation. The flame
monitor's compact design integrates the flame scanner and amplifier into one
compact housing. This greatly reduces overall cost and simplifies installation.
Additional costs normally required for mounting the control electronics in a
service cabinet or separate housing unit are no longer applicable.
The D-LX 100 Compact Flame Monitor has been developed to monitor flames in
single burner systems. The integrated relay output may be used to interface
with the fuel control valve. Applications for the D-LX 100 range from small
heating plants to process combustion systems.
[back to top]
|
|
Function
|
|
After start-up, the D-LX 100 Compact Flame Monitor
performs a self test. This
test will be repeated continuously during operation. This technique provides
complete and continuous self-checking capability to ensure proper and safe
operation. The flames radiation intensity is converted by a high sensitive
semiconductor photo element into an electrical flame signal. Only those signals
are processed by the advanced dual-microprocessor system which correspond to
flame flickering. Thus flame monitoring is not influenced by ambient light, as
far as constant light is concerned. The flame recognition threshold of the
D-LX
100 can be adjusted in the field using a manual switch. The flame failure
response time can be set to either 1, 3 or 5 seconds. The flame intensity
signal is available as an analog output. Status LEDs are provided so that the
operator may easily diagnose any fault.
[back to top]
|
|
Design
|
Options
|
|
The D-LX 100 Compact Flame Monitor is designed for years of trouble-free
service and built into a rugged NEMA 4x (IP 67) metal case.
For adapting the D-LX 100 Compact Flame Monitor to all technically significant
burner types, fuels and firings, several flame monitor types with different
spectral ranges are available.
[back to top]
|
The standard
Flame Intensity
current output is 0-20 mA; 4-20 mA is also available.
The standard front panel cover is metal; transparent plastic is also available.
The standard Safety Time setting is 1 s; 3 s or 5 s are also available.
|
|
D-LX 100 UA/UAF Ultraviolet
Flame Monitor
|
D-LX 100 IG/IS Infrared
Flame Monitor
|
|
These flame monitors have a spectral sensitivity of either 190 to 520 nm or 280
to 410 nm. All blue-burning flames may be monitored by these flame monitors.
Flames whose UV-radiation is absorbed by dust, water vapor or other materials,
and which cannot normally be monitored by UV-tubes, may be monitored by these
highly sensitive semiconductor UV-photo elements. These flame monitors have also
proven themselves in monitoring gas and oil combustion systems employing NOx
reduction techniques such as flue gas recirculation.
[back to top]
|
These IR flame monitors have a spectral sensitivity of either 300 to 1100 nm or
780 to 1800 nm, depending on the model. These flame monitors are ideally suited
for monitoring yellow-burning flames of coal or wood, which have no or only
very small portions of UV emissions. For monitoring oil flames, IR flame
monitors are ideally suited, also when additional fuels are burned.
|
|
D-ZS 087-20 Setup Utility
|
|
|
A D-ZS 087-20 Digital Display can be connected to the
D-LX 100 Compact Flame
Monitor. Using this utility, the installation and adjustment of the
D-LX 100
Compact Flame Monitor is greatly eased. By displaying the current flame
intensity, the D-LX 100 Compact Flame Monitor can be aligned optimally to the
flame. Further information such as minimum and maximum flame intensity are
displayed as well as a recommended setting for the response threshold.
[back to top]
|
|
Available Accessories
|
-
D-NG 24/05: AC power supply for operation of two
D-LX 100 Compact Flame Monitors at 115/230 V ac + 10% 15%, 42-60 Hz
-
D-ZS 087-20: Digital display device for alignment of the flame scanner; measures flame intensity and stores peak values
-
D-ZS 118: Optical aid for alignment of the ball-type adjustment flange on the sighting tube
-
D-ZS 093: UV-A, UV-B and IR light source for testing purposes 230 V / 50 Hz
-
D-ZS 033-1: Ball-type adjustment flange for the
D-LX 100
-
D-ZS 117-1: Heat insulator with potential separation
-
D-ZS 133-1: Ball valve for closing the sighting tube
[back to top]
|